Answer before reviewing
Choose the one best answer for the situation as written. Then read why each other option falls short.
No sign-up needed
20 questions, each with a clear explanation.
Question review
Try the set above first, then use this list to review. Each answer and explanation stays closed until you open it.
Correct answer: C · 12.5 amperes
For a resistive load, power in watts equals volts times amperes; NIST's guide to SI units defines the volt as one watt per ampere. Rearranged, current equals watts divided by volts: 1,500 W ÷ 120 V = 12.5 A. Dividing by 240 volts, a supply this heater isn't rated for, gives 6.25 amperes. Fifteen amperes is a common branch-circuit rating, not the heater's own draw. The 0.08 figure comes from dividing volts by watts, which turns the formula upside down.
Look for this next time: For a resistive load, current equals watts divided by volts, so a 1,500-watt, 120-volt heater draws 12.5 amperes.
Correct answer: A · It must open all of the ungrounded service conductors at the same time
OSHA's workplace electrical standard (29 CFR 1910.304(e)) requires each service disconnecting means to simultaneously disconnect all ungrounded conductors, so opening them one at a time falls short, labeled or not. The same rule requires the disconnect to plainly indicate whether it is open or closed, and to sit at a readily accessible location nearest the point where the service-entrance conductors enter, not well away from it. Opening every ungrounded conductor in one operation is what lets a single switch de-energize the building's wiring.
Look for this next time: A service disconnect opens all ungrounded conductors together, shows whether it is open or closed, and sits where the service conductors enter.
Correct answer: D · For no more than 90 days, and then it is removed
OSHA's temporary wiring rule (29 CFR 1910.305(a)(2)) allows temporary power and lighting installations of 600 volts or less for a period not to exceed 90 days for Christmas decorative lighting, carnivals and similar purposes, and it requires temporary wiring to be removed as soon as its purpose is complete. A season that runs past 90 days doesn't stretch the limit. Thirty days is shorter than the rule, and no monthly inspection turns temporary wiring into a one-year installation. ICC lists temporary service wiring in its Services and Service Equipment area, so look up how your NEC edition words the rule.
Look for this next time: Temporary wiring for holiday decorative lighting is limited to 90 days and comes down when its purpose ends.
Correct answer: B · 80 amperes
At unity power factor, volt-amperes equal watts, and NIST defines the volt as one watt per ampere, so current is volt-amperes divided by volts: 19,200 VA ÷ 240 V = 80 A. Dividing by 120 volts, half the feeder voltage, gives 160 amperes. Forty amperes comes from dividing by 480 volts, double the feeder voltage. Eight amperes is the same arithmetic with the decimal point in the wrong place. Exams often state the power factor: Minnesota's exam guide says its questions assume unity power factor unless a question says otherwise.
Look for this next time: At unity power factor, current equals volt-amperes divided by volts: 19,200 VA at 240 volts is 80 amperes.
Correct answer: D · GFCI protection for the workers who plug into them
OSHA's construction standard (29 CFR 1926.404(b)(1)) requires approved ground-fault circuit interrupters for personnel protection on all 120-volt, single-phase, 15- and 20-ampere receptacle outlets on construction sites that are not part of the permanent wiring and are in use by employees. The only alternative it allows is an assured equipment grounding conductor program, which this employer doesn't run. A larger grounding conductor is not one of the two protections the rule allows. A rating label is information, not protection, and a weatherproof cover keeps water out without addressing a ground fault.
Look for this next time: Temporary 120-volt, 15- and 20-ampere receptacles that workers use on a construction site need GFCI protection unless the employer runs an assured grounding program.
Correct answer: B · The swap reverses designated polarity, and the rule doesn't allow that
OSHA's workplace electrical standard (29 CFR 1910.304(a)(2)) says no grounded conductor may be attached to any terminal or lead so as to reverse designated polarity. A lamp lights either way because the circuit is complete, so a working lamp proves nothing about polarity. Polarity matters because equipment is built around it: the same standard connects the grounded conductor to a lampholder's screw shell, and reversed polarity at the receptacle can put the ungrounded conductor on the shell of a plug-in lamp instead. The circuit's ampere rating doesn't change the rule, and a connected grounding conductor doesn't correct swapped circuit conductors.
Look for this next time: Never land the grounded conductor where it reverses designated polarity; a device that still works can still be miswired.
Correct answer: A · About 4.8 amperes flows, too little to trip the breaker, so the pole stays energized
Ohm's law gives the fault current: NIST defines the ohm as one volt per ampere, so 120 V ÷ 25 Ω = 4.8 A. That is far below the breaker's 20-ampere rating, so the breaker has no reason to open, and the pole stays energized for anyone who touches it. OSHA's workplace electrical standard (29 CFR 1910.304(g)(5)) requires the path to ground from circuits, equipment and enclosures to be permanent, continuous and effective, and a rod alone fails the last test here. The fix is an equipment grounding conductor run with the circuit. Current does flow through the rod, and 3,000 amperes comes from multiplying instead of dividing.
Look for this next time: Earth alone is a poor fault path: 120 volts across 25 ohms drives only 4.8 amperes, so a 20-ampere breaker never opens.
Correct answer: C · 4 volts
Voltage drop is current times resistance, from the unit relationship NIST gives, an ohm being one volt per ampere: 16 A × 0.25 Ω = 4 V. The 0.25 ohm already covers both conductors, the outgoing one and the return, so doubling it again to reach 8 volts counts the return path twice. Sixty-four volts comes from dividing the current by the resistance instead of multiplying. 0.4 volt has the right digits with the decimal point in the wrong place. On a 120-volt circuit, 4 volts is about 3.3% of the supply voltage.
Look for this next time: Voltage drop equals current times the total resistance of the conductors that carry it.
Correct answer: B · 3.5 feet
OSHA's Table S-1 (29 CFR 1910.303(g)(1)) sets working-space depth by the nominal voltage to ground and by what sits on the far side of the space. For 151 to 600 volts to ground, the depth is 3 feet with no live or grounded parts opposite, 3.5 feet with grounded parts opposite, and 4 feet with exposed live parts on both sides. A grounded steel frame across the aisle makes this the middle case, so the answer is 3.5 feet. Three feet would apply with nothing grounded opposite and 4 feet with live parts on both sides, while 6.5 feet is the minimum headroom, not a depth.
Look for this next time: Working-space depth depends on voltage to ground and what is opposite: at 151 to 600 volts, grounded parts across the aisle mean 3.5 feet.
Correct answer: D · 30 inches, or the equipment's width if that is greater
Under OSHA's working-space rule (29 CFR 1910.303(g)(1)), the width of the working space in front of electric equipment is the width of the equipment or 30 inches, whichever is greater, and the space must let equipment doors or hinged panels open at least 90 degrees. A 20-inch panelboard therefore needs 30 inches, so stopping at the panel's own width is too narrow. Twenty-four inches is the minimum width of an entrance to the working space around equipment rated 1,200 amperes or more and over 6 feet wide, a different rule. Thirty-six inches is not part of the width rule.
Look for this next time: Working-space width is 30 inches or the equipment's width, whichever is greater, with room for doors to open at least 90 degrees.
Correct answer: A · That use isn't permitted; install fixed wiring and a receptacle in that room
OSHA's workplace electrical standard (29 CFR 1910.305(g)(1)) lists uses that flexible cords are not permitted for, including as a substitute for the fixed wiring of a structure and where run through holes in walls, ceilings or floors. A cord through a wall to serve the next room is both, so the answer is fixed wiring to a receptacle in that room. Sealing the hole, choosing a heavier cord type or keeping the cord short changes none of those prohibitions. The same list also rules out cords run through doorways or windows, attached to building surfaces or concealed behind walls.
Look for this next time: Flexible cords never replace fixed wiring, and they don't pass through walls, ceilings, floors, doorways or windows.
Correct answer: C · Close it effectively, for example with a knockout closure plug
OSHA's workplace electrical standard (29 CFR 1910.305(b)(1)) says unused openings in cabinets, boxes and fittings shall be effectively closed. A closure made for the purpose, such as a knockout plug, does that. Electrical tape is not a durable closure for a hole in a metal box, and no rule treats an open knockout as ventilation for the box. Mounting height doesn't matter either, because the requirement applies wherever the box is installed.
Look for this next time: Every unused opening in a box, cabinet or fitting must be effectively closed.
Correct answer: D · Live parts at 50 volts or more must be guarded against accidental contact
OSHA's workplace electrical standard (29 CFR 1910.303(g)(2)) requires live parts of electric equipment operating at 50 volts or more to be guarded against accidental contact, by approved cabinets or enclosures, or by location: a room open only to qualified persons, permanent partitions, an elevated platform, or an elevation of 8 feet or more. A busy walkway meets none of those, so the cover goes back on. Warning signs mark the entrances to guarded locations; they don't replace a guard. The 600-volt figure is wrong, and guarding applies whenever the parts are live, not only during service.
Look for this next time: Live parts at 50 volts or more need a guard, an enclosure, or a location that only qualified persons can reach.
Correct answer: A · The screw shell, the threaded part the lamp base turns into
OSHA's workplace electrical standard (29 CFR 1910.305(j)(1)) says that where a screw-shell lampholder is supplied by a circuit having a grounded conductor, the grounded conductor shall be connected to the screw shell. That leaves the ungrounded conductor on the center contact, so the center contact is the wrong place for the neutral. Alternating current does reverse direction, but the conductors keep their roles, so either terminal won't do. The mounting strap isn't a circuit terminal; grounding the fixture is the job of the equipment grounding conductor.
Look for this next time: In a screw-shell lampholder, the grounded conductor goes to the screw shell and the ungrounded conductor to the center contact.
Correct answer: B · One that is weatherproof whether or not the plug is inserted
OSHA's workplace electrical standard (29 CFR 1910.305(j)(2)) separates two wet-location cases. Where the product plugged in is not attended while in use, such as landscape lighting, sprinkler controllers and holiday lights, the enclosure must be weatherproof with the attachment plug inserted or removed. Where the product is attended while in use, such as a portable tool, the enclosure must be weatherproof when the plug is removed, which fits a different situation. A GFCI receptacle protects people from ground faults but doesn't make the enclosure weatherproof, and an ordinary flush plate isn't a weatherproof enclosure.
Look for this next time: A wet-location receptacle that serves an unattended load needs an enclosure that stays weatherproof with the plug inserted.
Correct answer: C · Grouped together and identified as the disconnecting means for that appliance
OSHA's workplace electrical standard (29 CFR 1910.305(j)(3)) requires a means to disconnect each appliance from all ungrounded conductors, and when an appliance is supplied by more than one source, the disconnecting means must be grouped and identified. A disconnect on only one circuit, or only on the larger one, leaves the appliance energized from the other circuit. Labels on disconnects scattered around the building don't meet the grouping requirement, and a worker servicing the appliance could miss one of them.
Look for this next time: An appliance fed from more than one source needs all of its disconnects grouped and identified.
Correct answer: A · Legibly mark each disconnect to show which unit it serves
OSHA's workplace electrical standard (29 CFR 1910.303(f)) requires each disconnecting means for motors and appliances to be legibly marked to indicate its purpose, unless it is located and arranged so the purpose is evident, and the marking must be durable enough for its environment. Six identical switches in a row serving units spread across a roof make the purpose anything but evident, so each one needs its own marking. Marking only the end switches leaves four unidentified, and a list kept indoors isn't on the disconnect where someone needs it.
Look for this next time: Each motor or appliance disconnect is legibly and durably marked with its purpose unless its location makes the purpose evident.
Correct answer: B · It must be in sight: visible and no more than 50 feet away
OSHA's workplace electrical standard (29 CFR 1910.305(j)(4)) requires a disconnecting means located within sight of the controller location, and it defines within sight as visible and not more than 50 feet from the other piece of equipment. A disconnect 75 feet away and out of view fails on both counts. The rule doesn't require the disconnect to share the controller's enclosure, because within sight is enough. No 100-foot allowance exists, and mounting height has nothing to do with this requirement.
Look for this next time: A motor controller's disconnecting means must be within sight of it: visible and no more than 50 feet away.
Correct answer: D · It isn't allowed; emergency wiring stays independent except at transfer equipment
OSHA's workplace electrical standard (29 CFR 1910.308(b)) requires emergency circuit wiring to be kept entirely independent of all other wiring and equipment. It may not enter the same raceway, cable, box or cabinet as other wiring, except where common circuit elements are required or for transferring power from the normal to the emergency source. Sharing a conduit with normal lighting circuits is exactly what the rule prohibits, so color coding, matching voltage or spare conduit fill doesn't make it acceptable. Separate wiring keeps a fault on the normal circuits from reaching the emergency lighting through a shared raceway.
Look for this next time: Emergency circuit wiring stays independent of other wiring and shares enclosures only where power transfers between sources.
Correct answer: C · Class II, because the hazard is combustible dust
OSHA's definitions (29 CFR 1910.399) separate hazardous locations by the material present. Class I locations have flammable gases or vapors. Class II locations are hazardous because of combustible dust, and OSHA names grain handling and processing plants among its examples. Class III locations have easily ignitable fibers or flyings that are not likely to be suspended in the air. Grain dust suspended during normal operation is therefore a Class II hazard. An explosive mixture alone doesn't make an area Class I, because the class follows the material, and a food product can still be a combustible dust.
Look for this next time: Hazardous location classes follow the material: Class I gases and vapors, Class II combustible dust, Class III fibers and flyings.
Use the sample well
A short set can show you what deserves another look. A strong run shows you can do what a journeyman exam asks: spot the condition that decides a code question, then apply the rule or the formula. Twenty questions are a small sample, so the result does not predict a pass on your state's exam.
Choose the one best answer for the situation as written. Then read why each other option falls short.
Confirm why the best option fits, even when you were right.
Use recurring misses—not one score—to choose your next focus.
Full Journeyman Electrician prep
Want more than 20 questions?
At launch: 375 exam-style Journeyman Electrician questions and 500 flashcards, practiced one content area at a time.
Explore Full Journeyman Electrician PrepFree Journeyman Electrician resources
Open the exam overview, build a study plan, or browse the Journeyman Electrician guides.
Review the exam format, official sources, and preparation options.
Open exam hub →Practical planning aidTurn the time you have into a clear study rhythm.
Build my outline →Source-backed answersGo straight to the question already on your mind.
Browse guides →